F46 high temperature resistant oil resistant special cable
- Tel:18019899982
- Fax:0550-7989666
- Mail:tkjd@tiankang.com
Description
Product Description: |
Product features: This product is applicable to metallurgical, petroleum, chemical and power plants and other mining enterprises. It can be used as a connecting line for various electrical appliances, meters and automatic devices under high temperature and harsh environment (such as acid, alkali and oil-water low temperature conditions). It can be used for control, monitoring and protection circuit under AC rated voltage 450/750 volts or below. Type and name: |
Serial number | Model | Name |
One | KFF | Fluorine plastic insulated and sheathed control cables |
Two | KFFP | Fluoroplastic insulated and sheathed shielded control cable |
Three | KFFR | Fluoroplastic insulated and sheathed control flexible cables |
Four | KFFRP | Fluoroplastic insulated and sheathed shielded control flexible cables |
Five | KFV | Fluorine plastic insulated PVC sheathed control cable |
Six | KFVP | Fluorine plastic insulated PVC sheathed control cable |
Seven | KFVR | Fluoroplastic insulated PVC sheathed control flexible cable |
Eight | KFVRP | Fluoro plastic insulated PVC sheathed control soft cable |
Nine | KFV22 | Fluorocarbon plastic insulated PVC sheathed steel tape armored control cable |
Ten | KFVP22 | Fluorine plastic insulated PVC sheathed steel tape armoured shielding control cable |
Eleven | KFVR22 | Fluorocarbon plastic insulated PVC sheathed steel tape armored control flexible cable |
Twelve | KFVRP22 | Fluoroplastic insulated PVC sheathed steel tape armoured shielded control soft cable |
Thirteen | KFFV22 | Fluorocarbon plastic insulated and sheathed PVC sheathed steel sheathed control cables |
Fourteen | KFFRV22 | Fluorocarbon plastic insulated and inner sheath PVC sheathed steel belt armored control soft cable |
Usage characteristics:
1, rated voltage: AC Uo/U; 450/750V
2, working temperature: serial number 1~4 -60 ~ +200 C
The serial number is 5~14 -15 to +105 C.
3, insulation resistance (20 C) not less than 50M ohm. Km
4. DC resistance of conductor core (20 C) meets the requirements of GB3956-97.
5. The allowable bending radius of the armored cable is not less than 6 times of the outer diameter of the cable, and the allowable bending radius of the armoured cable is not less than 12 times of the outer diameter of the cable.
6. Installation temperature: No. 1~4 -45 C.
The serial number is 5~140 degrees.
Reference data for size and size:
Serial number | Nominal cross section | Conductor core specification | Conductor core specification | Cable core number | ||
Serial number 1, 2, 5, 6, 9, 10, 13 | Serial number 3, 4, 7, 8, 11, 12, 14 | Serial number 1~4 | Serial number 5~8 | Serial number 9~14 | ||
One Two Three Four Five | Zero point two Zero point five Zero point seven five One One point five Two point five | 1/0.52 1/0.80 1/1.0 1/1.13 1/1.38 1/1.76 | 7/0.20 16/0.20 19/0.23 24/0.20 19/0.26 32/0.20 19/0.32 30/0.25 49/0.26 | 2~44 2~30 2~19 2~16 2~14 2~8 | 2~61 | 7~37 7~37 7~37 4~37 |