ZR-KVVP, ZR-KYJVP flame retardant control cable

Plastic insulated (PVC insulated and XLPE insulate
  • Tel:18019899982
  • Fax:0550-7989666
  • Mail:tkjd@tiankang.com
Description

ZR-KVVP, ZR-KYJVP flame retardant control cable
Executive standard
GB/T 9330-2008 plastic insulated control cable
General rules for GB/T19666-2005 flame retardant and fire resistant wire and cable
purpose
Plastic insulated (PVC insulated and XLPE insulated) sheath control cables are used for occasions such as AC rated voltage 0.6/1kV, 450/750V control, monitoring circuit and protection circuit, etc., for power distribution and control of power plants and substations in power plants and substations, and for use in flame retardant requirements.
Name of other flame retardant cables

Table 1
Type numberName
ZR-KVVCopper core PVC insulated PVC sheathed flame retardant control cable
ZR-KYJVCopper core XLPE insulated PVC sheathed flame retardant PVC control cable
ZR-KVVPCopper core PVC insulated braided shielding flame retardant control cable
ZR-KYJVPCopper core XLPE insulated copper wire braided shielded PVC sheathed flame retardant control cable
ZR-KVVP2Copper core PVC insulated copper tape shielded PVC sheathed flame retardant control cable
ZR-KYJVP2Copper core XLPE insulated copper tape shielded PVC sheathed flame retardant control cable
ZR-KVVP3Copper core PVC insulated copper tape shielded PVC sheathed flame retardant control cable
ZR-KYJVP3Copper core XLPE insulated copper tape shielded PVC sheathed flame retardant control cable
ZR-KVV22Copper core PVC insulated steel tape armoured PVC sheathed flame retardant control cable
ZR-KYJV22Copper core XLPE insulated steel tape armored PVC sheathed flame retardant control cable
ZR-KVV32Copper core PVC insulated fine steel wire armoured PVC sheathed flame retardant control cable
ZR-KYJV32Copper core XLPE insulated fine steel wire armoured PVC sheathed flame retardant control cable
ZR-KVVP2-22Copper core PVC insulated copper tape shielded steel tape armored PVC sheathed flame retardant control cable
ZR-KYJVP2-22Copper core XLPE insulated copper tape shielded steel tape armored PVC sheathed flame retardant control cable
ZR-KVVRCopper core PVC insulated PVC sheathed control flexible cable
ZR-KVVRPCopper core PVC insulated copper wire braided shielded PVC sheathed control flexible cable
DDZ-KVVCopper core PVC insulated PVC sheathed low halogen low smoke flame retardant control cable
DDZ-KVVPCopper core PVC insulated braid shielded low halogen low smoke flame retardant control cable
DDZ-KVVP2Copper core PVC insulated copper tape shielded low halogen low smoke flame retardant control cable
DDZ-KVV22Copper core PVC insulated steel tape armored low halogen low smoke flame retardant control cable
DDZ-KVV32Copper core PVC insulated fine steel wire armored low halogen low smoke flame retardant control cable
WDZ-KYJYCopper core XLPE insulated halogen free low smoke flame retardant control cable
WDZ-KYJYPCopper core XLPE insulated braided shielding sheath halogen free low smoke flame retardant control cable
WDZ-KYJYP2Copper core XLPE insulated copper tape shielded halogen free low smoke flame retardant control cable
WDZ-KYJY23Copper core XLPE insulated steel tape armored halogen free low smoke flame retardant control cable
WDZ-KYJY33Copper core XLPE insulated fine steel wire armored halogen free low smoke flame retardant control cable

Note: flame retardant (ZR) is divided into bundles A, B, C flame retardant, respectively, ZA, ZB and ZC, generally do not specify (ZR) level is C class, plus WDZ for low smoke halogen free cable.

 
Product specification
Table 2
Type numberrated
Voltage
V
Guide body nominal section mm2
Zero point fiveZero point seven fiveOneOne point fiveTwo point fiveFourSixTen

The rated voltage is U0/U 450/750V.
The long term allowable working temperature of PVC insulated conductor is 70 C; the long-term allowable working temperature of XLPE insulated conductor is 90 C;
The laying temperature of the cable should not be less than 0 degrees. The recommended allowable bending radius is:
The cable without armored layer should not be less than 6 times of the outer diameter of the cable.
The cable with armored or copper shielded structure shall be not less than 12 times the outer diameter of the cable.
The soft cable with shielding structure should be not less than 6 times the cable.
By color recognition, the insulation cores of 5 core and below cables are colored or digital.
By digital recognition, from the inner layer to the outer layer, it starts clockwise in the order of natural numbers starting from 1, and the color of the digital logo should be obviously different from the insulation color.
Main technical specifications of cables
1. When the conductor is 20 degrees, the large DC resistance is shown in Table 3.
Table 3 large DC resistance / Omega /km at 20 degree conductor

Nominal cross section of conductor
Mm2
Conductor category
1 kinds2 kinds5 kinds
Large DC resistance of 20 /km
Zero point fiveThirty-sixThirty-sixThirty-nine
Zero point seven fiveTwenty-four point fiveTwenty-four point fiveTwenty-six
OneEighteen point oneEighteen point oneNineteen point five
One point fiveTwelve point oneTwelve point oneThirteen point three
Two point fiveSeven point four oneSeven point four oneSeven point nine eight
FourFour point six oneFour point six oneFour point nine five
SixThree point zero eightThree point zero eightThree point three zero
TenOne point eight threeOne point eight threeOne point nine one


2. AC withstand voltage test for power frequency is shown in Table 4.
Table 4 voltage test

Rated working voltage
Item
 

450/750V
AC voltage frequency
Test time
Test voltage
test result
50Hz
5 minutes
3000V
No breakdown
50Hz
5 minutes
3500V
No breakdown


3. Insulation resistance at working temperature is shown in Table 5.
Table 5 insulation resistance at a permissible operating temperature

Nominal cross section of conductor
Mm2
Small insulation resistance M Omega.Km
PVC insulation (70 C)XLPE insulation (90 C)
1 kinds2 kinds5 kinds1 kinds2 kinds
Zero point five--Zero point zero one three--
Zero point seven fiveZero point zero one twoZero point zero one fourZero point zero one oneOne point twoOne point four
OneZero point zero one oneZero point zero one threeZero point zero one zeroOne point oneOne point three
One point fiveZero point zero one oneZero point zero one zeroZero point zero one zeroOne point oneOne
Two point fiveZero point zero one zeroZero point zero zero nineZero point zero zero nineOneZero point nine
FourZero point zero zero eight fiveZero point zero zero seven seven-Zero point eight fiveZero point seven seven
SixZero point zero zero seven zeroZero point zero zero six five-Zero point seven zeroZero point six five
Ten-Zero point zero zero six five--Zero point six five

4, flame retardancy
The flame-retardant properties should be tested by A, B or C in the prescribed burning of GB/T18380.33 ~ 35. If the user fails to make a request, according to the requirements of the C test, it will meet the requirements specified in Table 6.
Table 6 requirements for bunched combustion

Code nameVolume of test metal material (L/m)Fire time /minConformity index
ZA
ZB
ZC
ZD*
Seven
Three point five
One point five
Zero point five
Forty
Forty
Twenty
Twenty
1) the length of carbon is not greater than 2.5m.
2) after the fire is stopped, the trapping time is less than 1 hours.
ZD - only for wires and cables whose outer diameter is less than 12mm.