Guide rail temperature transmitter

The temperature transmitter amplifies the thermal
  • Tel:18019899982
  • Fax:0550-7989666
  • Mail:tkjd@tiankang.com
Description

First, product introduction

The temperature transmitter amplifies the thermal resistance or thermocouple signals in the field and processes them to the control system, which is used as the automatic compensation function of the cold junction temperature when the thermocouple is transferred to the temperature. It can be used in conjunction with units such as instruments and DCS, PLC, and so on. It can provide signal isolation, signal conversion, signal distribution, signal processing and so on, so as to improve the anti-interference ability of the industrial production process automatic control system and ensure the stability and reliability of the system. This product is divided into one in one out, one in two out, two in two out, and input and output magnetic isolation.

Two, display panel appearance structure diagram

 Structure diagram.Png


35mm guide rail installation. Please note that the card position is stable and firm when installed. Please install vertically as far as possible, so as to facilitate the heat release inside the meter.


Three, wiring diagram

 Wiring diagram.Png


Four, technical parameters

input


Input signal

Two or three wire thermal resistor and thermocouple (signal type and measuring range can be programmed through the corresponding host computer software).

output


output signal

4-20mA, 0-10mA, 0-20mA, 1-5V, 0-5V

Output load

4-20mA, 0-10mA, 0-20mA load resistance RL is less than 400 ohms; 1-5V and 0-5V load resistance RL is greater than 250K 250K.

Power Supply


Power Supply

DC20-32V

Power waste

One input and one output power: less than 1W;


One input, two output, two input and two output power: less than 1.4W

Other parameters


Insulation resistance (input / output / power supply)

More than 100M ohm (500VDC)

Insulation strength (input / output / power supply)

1500Vrms (1 min, no spark)

working temperature

-10 ~ 50 C (no condensation, no ice).

relative humidity

25% ~ 85%RH

Storage temperature

-10 ~ 60 C (no condensation, no ice).

temperature drift

0.0075%FS/ C

Installation mode

35mmDIN guide rail installation

Installation dimension

13*108*121.2mm (wide * high * Deep)

Transmission accuracy (20 C)

0.2%FS + 1 words

Resolving power

0.1 C

Internal cold junction compensation temperature range

-10 ~ 50 C

Cold end compensation accuracy

+ 1 c

response time

50ms reaches 90% of its final value.

weight

About 130 grams.

electromagnetic compatibility

Comply with GB/T18268 industrial equipment application requirements (IEC 61326-1)

Applicable field equipment

Two or three wire thermal resistor and thermocouple sensor

 

Five. Input signal type table:

Code

Signal type

measuring range

Code

Signal type

measuring range

Zero

Thermocouple B

400~1800 C

Eleven

Thermal resistance Cu50

-50.0 ~ 150 C

One

Thermocouple S

0~1600 C

Twelve

Thermal resistance Cu53

-50.0 ~ 150 C

Two

Thermocouple K

0~1300 C

Thirteen

Thermal resistance Cu100

-50.0 ~ 150 C

Three

Thermocouple E

0~1000 C

Fourteen

Thermal resistance Pt100

-200.0 ~ 650 C

Four

Thermocouple T

-200.0 ~ 400 C

Fifteen

Thermal resistance BA1

-200.0 ~ 600 C

Five

Thermocouple J

0~1200 C

Sixteen

Thermal resistance BA2

-200.0 ~ 600 C

Six

Thermocouple R

0~1600 C

Seventeen

0~400 ohm linear resistance

-1999 ~ 9999

Seven

Thermocouple N

0~1300 C

Nineteen

30~350 ohm long range resistor

-1999 ~ 9999

Eight

F2

700~2000 C

Twenty

0 ~ 20mV

-1999 ~ 9999

Nine

Thermocouple Wre3-25

0~2300 C

Twenty-two

0 ~ 100mV

-1999 ~ 9999

Ten

Thermocouple Wre5-26

0~2300 C